Essential Services Inspection Guide
Essential Service
|
BCA Code & Standard
|
Maintenance Standard
|
| Air conditioning systems |
AS 1668 |
Monthly to AS 1851.6, AS 3666 |
| Emergency lifts |
BCA E3.4, AS 1735.2 |
Weekly to OH&S Standards |
| Emergency lighting |
BCA Part E4, AS2293.1 |
6 monthly to AS 2293.2 |
| Emergency power supply |
BCA Spec G3.8 |
6 monthly |
| Emergency warning and intercommunication
systems |
BCA E4.9, Spec E1.5, Spec E1.7, AS 2220 |
Monthly as AS 1851.10 |
| Exit doors |
BCA Section D |
3 monthly inspection to confirm exit doors are
intact, operational and fitted with conforming hardware |
| Exit signs |
BCA Part E, AS 2293.1 |
6 monthly to AS 2293.2 |
| Fire brigade connections |
BCA Spec E1.7, Vic H101.9, Vic H103, AS 1670 |
Weekly to AS 1851.8 |
| Fire Alarm Systems |
BCA Spec E1.7 AS 1670 |
Weekly to AS 1851.8 |
| Fire Extinguishers |
BCA E1.6, AS 2444 |
6 monthly to AS 1851.1 |
| Fire Hose Reels |
BCA E1.4 |
6 monthly to AS 1851.2 |
| Fire Hydrants |
BCA E1.3, AS 2419.1 |
Weekly to AS 1851.4 |
Abridged list only. For